IEEE Power & Energy Society General Meeting - IEEE PES GM 2015, Denver (United States of America). 26-30 July 2015
Summary:
This paper investigates whether existing protection schemes would detect an open phase fault in the power supply systems of a 1092 MW Spanish nuclear power generating station. This investigation follows to the 2012 event at unit 2 of Byron station, Illinois, USA. Symmetrical components method is proposed to draw fundamental conclusions. The results of the symmetrical components analysis are validated using EMTP simulations.
Keywords: Open phase fault, nuclear power generating station, power supply systems, symmetrical components, EMTP simulation
Publication date: 2015-07-26.
Citation:
L. Rouco, A. Pontes Jiménez, J. Archilla Martín-Sanz, Open phase faults in the external power supply systems of a nuclear power generating station: symmetrical components analysis and EMTP validation, IEEE Power & Energy Society General Meeting - IEEE PES GM 2015, Denver (United States of America). 26-30 July 2015.